Delta P Control Calibration
The only user calibration is the zero adjustment of
the display. Due to slight changes in electronic
components over time, or pressure differentials
within the plant environment, the display may read
something other than 0.0 while at rest. Use the
following procedure to recalibrate the operating
system.
1. Turn power to the Delta P Control ON for a
minimum of 30-minutes to stabilize the
operating temperature.
2. Turn power to the control OFF.
P. Press and hold the LOW SET, HIGH SET, and
ALARM SET keys while turning power to the
control back ON. Continue holding the keys as
the control goes through its power-up sequence.
The number 8 is displayed in each digit, and
then the display reads 0.0.
4. Release the three keys. The new calibration is
automatically stored in memory.
Caution!
The compressed-air supply must be
oil and moisture free. Contamination
in the compressed air used to clean
filters will result in poor cleaning,
cleaning valve failure or poor
collector performance.
Purge compressed-air lines to remove
debris before connecting to the unit’s
compressed-air manifold.
Turn compressed-air supply OFF and
bleed lines before performing service
or maintenance work.
1. Remove the plastic pipe plug from the unit’s air
manifold and connect the compressed-air
supply line. Use thread-sealing tape or pipe
sealant on all compressed-air connections.
Compressed Air Installation
Optional Settings
2PMJVolt Power Supply
To operate at 230-Volt, remove two jumpers
labeled W1 and W3. Reinsert one of the jumpers in
position W2.
Change from English to Metric (SI) Units
On the J1 jumper block located above the PROG
DISABLE terminals, move the jumper from the
center and left pins 2 and 3, to the center and right
pins 1 and 2.
Disable Setpoint Adjustment
To restrict setpoint changes, install a jumper wire
across the PROG DISABLE terminals on Terminal
Block 2, TB2. The current settings can be
displayed, but no changes can be made until the
jumper is removed. A key-operated, normally-
closed switch installed in the enclosure door will
provide temporary access to the setting functions
without opening the door.
External Alarm Reset
Wire the ARM RESET terminals on Terminal Block 2,
TB2, to a key-operated, normally-open switch.
Closing the switch turns the alarm OFF. If alarm
conditions still exist, the alarm relay re-activates in
10 seconds.
Alarm Disable
Remove the jumper on Jumper Block J5 located on
the lower-right quadrant of the circuit board, from
the ALARM mode position.
1. Reinstall the jumper in the SLAVE mode
position to operate the AUXILIARY relay in
parallel with the HI/LO CONTROL relay.
2. The AUXILIARY relay will not function if no
jumper is installed.
Note: Disabling the alarm relay reduces the
alarm function to visual display only.
Analog Output
Locate the Sensor Out Terminal Block 4, TB4, in
the upper-left quadrant of the circuit board. This
connector provides a 1 to 5-Volt DC output
proportional to the 0-to-maximum span of the
pressure sensor. This circuit requires a 10,000-ohm
load minimum.